FIRE PROTECTION SYSTEM \ CLEAN AGENT SYSTEM
ATUM227 (HFC227ea System)
SPECIFICATIONS
SYSTEM MODEL |
ATUM227 |
Design Standard |
BS EN 15004-1 / NFPA 2001 |
Extinguishing Agent |
HFC227ea |
Propellant |
Nitrogen Super-pressurization |
Storage Pressure |
360psi (25bar) @ 70°F (21°C) |
Cylinder Sizes |
15L - 180L Welded Cylinders |
Cylinder Test Pressure |
885psi (61bar) |
Cylinder Valve |
Pressure Differential Piston with Over-pressure Relief Device |
Release Devices |
Manual / Pneumatic / Electric |
Release Condition |
Cross-Zone / Manual |
EFS / PFS (HFC227ea System)
SPECIFICATIONS
RATIO FLOW CONTROLLER |
SYSTEM MODEL |
EFS |
PFS |
Design Standard |
UL 2166 / NFPA 2001 |
Extinguishing Agent |
HFC227ea |
Storage Pressure |
360psi (25bar) @ 70°F (21°C) |
Cylinder Sizes |
27L - 175L |
63L - 175L |
Cylinder Test Pressure |
1000psi (69bar) |
Propellant |
Agent Cylinder Nitrogen Super-pressurization |
Agent Cylinder Nitrogen Super-pressurization with Supplementary 68L Nitrogen Cylinder (60/70/80bar) |
Cylinder Valve |
Pressure Differential Piston with Over-pressure Relief Device |
Release Devices |
Manual / Pneumatic / Electric |
Release Condition |
Cross-Zone / Manual |