FIRE PROTECTION SYSTEM \ CLEAN AGENT SYSTEM

ATUM227 (HFC227ea System)
GSFP

SPECIFICATIONS

SYSTEM MODEL ATUM227
Design Standard BS EN 15004-1 / NFPA 2001
Extinguishing Agent HFC227ea
Propellant Nitrogen Super-pressurization
Storage Pressure 360psi (25bar) @ 70°F (21°C)
Cylinder Sizes 15L - 180L Welded Cylinders
Cylinder Test Pressure 885psi (61bar)
Cylinder Valve Pressure Differential Piston with Over-pressure Relief Device
Release Devices Manual / Pneumatic / Electric
Release Condition Cross-Zone / Manual
EFS / PFS (HFC227ea System)
GSFP

SPECIFICATIONS

RATIO FLOW CONTROLLER
SYSTEM MODEL EFS PFS
Design Standard UL 2166 / NFPA 2001
Extinguishing Agent HFC227ea
Storage Pressure 360psi (25bar) @ 70°F (21°C)
Cylinder Sizes 27L - 175L 63L - 175L
Cylinder Test Pressure 1000psi (69bar)
Propellant Agent Cylinder Nitrogen Super-pressurization Agent Cylinder Nitrogen Super-pressurization with Supplementary 68L Nitrogen Cylinder (60/70/80bar)
Cylinder Valve Pressure Differential Piston with Over-pressure Relief Device
Release Devices Manual / Pneumatic / Electric
Release Condition Cross-Zone / Manual